145kv GIS Switchgear
Brief Description
1.Gas Insulated Switchgear (GIS) is 3-phase AC high voltage switchgear which is used for the control, measurement, protection and switching of transmission lines. Since 1984, more than 5000 bays have been in service, some exported to Thailand, Equatorial Guinea and other countries.
2.ZF12B -72.5/126/145 (L) GIS contains major substation equipments, such as circuit breaker, disconnector, earthing switch, voltage transformer, current transformer and surge arrester. All components are three-phase in one closure. In ZF12B, the disconnector and earthing switch combined into 3-working-position type DS/ES to optimize the equipment structure and make it more compact.
Main Features
145kv GIS Switchgear
1. ZF12B series are equipped with 3-working-position type DS/ES, which has the advantages of compactness, flexible configuration, physically mechanical interlock and high reliability.
2. The mechanism is oil/gas free, simple construction, easy maintenance and reliable operation.
3. The enclosure is made of aluminum alloy to ensure light weight, low temperature-rise and strong anti-corrosion.
4. Double sealing systems are adopted to guarantee high reliability in gas tightness and the annual gas leakage rate is leaa than 0.5%.
5. Excellent insulating, conducting and current carrying performances.
Specifications | Unit | Value | |||||
Rated voltage | kV | 72.5 | 126 | 145 | |||
Rated current | A | 2000/3150 | |||||
Rated frequency | Hz | 50/60 | |||||
Rated short-time withstand current (r.m.s) | kA | 40 | |||||
Rated peak withstand current | kA | 100/104 | |||||
1min rated power frequency withstand voltage (r.m.s) | To earth & between pole | kV | 140 | 230 | 275 | ||
Across isolating distance | kV | 160 | 265 | 315 | |||
Rated lightning impulse withstand voltage (peak) | To earth & between pole | kV | 325 | 550 | 650 | ||
Across isolating distance | kV | 375 | 630 | 750 | |||
Rated SF6 gas pressure(20℃) | CB compartment | MPa | 0.6 | ||||
Others | MPa | 0.4 | |||||
Rated SF6 annual leakage | % | ≤0.5 |